Welcome to PacificValves.com

HEATGUARD Tempering Valve AU Standard RMC

More Views

HEATGUARD Tempering Valve AU Standard RMC
RMC HEATGUARD Tempering Valve mixes hot water with cold water to deliver tempered water at a constant temperature throughout an entire house, building or system. Models available: MIX11009 (15mm) and MIX11012 (20 mm).

AUSTRALIAN STANDARD - AS4032.2
HEATGUARD Tempering Valve AU Standard RMC

MIX11009i Tempering Valve 15mm RMC

$83.80
  • Buy 20 for $62.80 each and save 25%
HEATGUARD Tempering Valve AU Standard RMC

Heatguard MIX11012i Tempering Valve 20mm RMC

$111.20
  • Buy 20 for $83.40 each and save 25%
OR

RMC HEATGUARD Tempering Valves that mixes hot water with cold water to deliver tempered water at a constant temperature throughout an entire house, building or system. Suitable for tempering the hot water supply to sanitary devices intended for personal hygiene purposes, where outlet temperature must not exceed a maximum of 50 C. This tempering valve is compatible with most storage water heaters and is provided with insulation.

Cold water supply temperature: 5°C - 30°C
Hot water supply temperature: 60°C - 90°C
Optimum outlet temperature range: 40°C - 50°C
Set temperature: Must be commissioned on site to achieve desired outlet temperature
Accuracy of outlet temperature: ±3° C – tested to AS4032.2 between 40°C and 50°C
Minimum temperature differential: (Between hot supply and outlet temperature) 15°C
Supply pressure, static: 1600 kPa maximum
Supply pressure imbalance, dynamic: (At time of commissioning) 2:1 maximum
Maximum permitted pressure variation in either supply, in order to control outlet temperature to ±3° C:
(From supply pressure at commissioning) ±10% maximum
Minimum flow rate: 4 litres/min.
Fittings Supplied Male BSP Thread

 

For use in hot water distribution systems. Fitting the valve at the hot water source ensures the delivery of constant temperature hot water throughout the system. Compatible with most storage water heaters. DO NOT USE on steam supplied systems.
Tempers the hot water supply to sanitary devices intended for personal hygiene purposes, where outlet temperature must not exceed a maximum of 50⁰C.
• Union connections - Valve easy to install and easy to remove for servicing of strainers • Performance - More accurate control of outlet temperature for safer installations • Strainers upstream of check valves - Protects valve and check valves from impurities in the water supply • Tamper-proof adjustment - Special adjuster key eliminates chances of accidental adjustment • Dezincification resistant - Meets Australian Standard for potable water supply • Individually tested and calibrated - Every valve is tested to ensure higher quality and performance Insulation provided
Heatguard is available in two size configurations:- MIX11009i - 15mm MIX11012i - 20mm