Heatguard MIX11012i Tempering Valve is suitable for tempering the hot water supply to sanitary devices intended for personal hygiene purposes, where outlet temperature must not exceed a maximum of 50 C. This tempering valve is compatible with most storage water heatersa and is provided with insulation.
Cold water supply temperature: 5°C - 30°C
Hot water supply temperature: 60°C - 90°C
Optimum outlet temperature range: 40°C - 50°C
Set temperature: Must be commissioned on site to achieve desired outlet temperature
Accuracy of outlet temperature: ±3° C – tested to AS4032.2 between 40°C and 50°C
Minimum temperature differential: (Between hot supply and outlet temperature) 15°C
Supply pressure, static: 1600 kPa maximum
Supply pressure imbalance, dynamic: (At time of commissioning) 2:1 maximum
Maximum permitted pressure variation in either supply, in order to control outlet temperature to ±3° C:
(From supply pressure at commissioning) ±10% maximum
Minimum flow rate: 4 litres/min.
Fittings Supplied Male BSP Thread